电机电抗器 西门子6SL3000-2BE32-1AA0
SINAMICS/MICROMASTER PX 电机电抗器用于 3AC 380-480V,50/60Hz,210A AC Drive/功率模块/ 电机模块
|
Output reactor
Output reactors reduce the rate of voltage rise (dv/dt) and the height of the current peaks, and enable longer motor cables to be connected.
Owing to the high rates of voltage rise of the fast-switching IGBTs, the capacitance of long motor cables reverses polarity very quickly with every switching operation in the inverter. As a result, the inverter is loaded with additional current peaks of substantial magnitude.
Output reactors reduce the magnitude of these additional peaks because the cable capacitance reverses polarity more slowly across the reactor inductance, thereby attenuating the amplitudes of the current peaks.
When using output reactors, the following should be observed:
Two output reactors are to be provided to increase the permissible cable lengths.
When connecting the Power Modules to IT networks, the use of an output reactor is recommended to avoid an overcurrent shutdown in the event of a ground fault.
|
Frame size |
||
---|---|---|---|
|
FSD |
FSE |
FSF |
PM240P?2 Power Module |
|||
Available output reactors |
|
|
|
|
? |
? |
? |
|
– |
– |
? |
Line voltage 380 ... 480 V 3 AC |
Output reactor |
||||
---|---|---|---|---|---|
|
6SE6400-3TC07-5ED0 |
6SE6400-3TC14-5FD0 |
6SL3000-2BE32-1AA0 |
6SL3000-2BE32-6AA0 |
|
Rated current |
A |
90 |
178 1) |
210 |
260 |
Power loss |
kW |
0.27 |
0.47 |
0.49 |
0.5 |
Connection to the Power Module |
|
Flat connector for M6 screw |
Flat connector for M8 screw |
Flat connector for M10 screw |
Flat connector for M10 screw |
Motor connection |
|
Flat connector for M6 screw |
Flat connector for M8 screw |
Flat connector for M10 screw |
Flat connector for M10 screw |
PE connection |
|
M6 screw |
M8 screw |
M8 screw |
M8 screw |
Cable length, max. between output reactor and motor |
|
|
|
|
|
|
m (ft) |
200 (656) |
200 (656) |
300 (984) |
300 (984) |
|
m (ft) |
300 (984) |
300 (984) |
450 (1476) |
450 (1476) |
Dimensions |
|
|
|
|
|
|
mm (in) |
270 (10.6) |
350 (13.8) |
300 (11.8) |
300 (11.8) |
|
mm (in) |
248 (9.76) |
321 (12.6) |
285 (11.2) |
315 (12.4) |
|
mm (in) |
209 (8.23) |
288 (11.3) |
257 (10.1) |
277 (10.9) |
Degree of protection |
|
IP20 |
IP20 |
IP00 |
IP00 |
Weight, approx. |
kg (lb) |
27 (59.5) |
57 (126) |
60 (132) |
66 (146) |
Suitable for |
Type |
6SL3210-1RE24-5 . L0 |
FSE:
FSF: |
6SL3210-1RE32-1 . L0 |
6SL3210-1RE32-5 . L0 |
|
|
FSD |
FSE/FSF |
FSF |
FSF |
1) On the rating plate of the reactor, the current is specified according to the duty cycle for high overload (HO). This is lower than the current specified according to the duty cycle for low overload (LO) of the Power Module.
Line voltage 500 ... 690 V 3 AC |
Output reactor |
||
---|---|---|---|
|
6SL3000-2AH31-0AA0 |
6SL3000-2AH31-5AH0 |
|
Rated current |
A |
100 |
150 |
Power loss |
kW |
0.3 |
0.34 |
Connection to the Power Module |
|
Flat connector for M10 screw |
Flat connector for M10 screw |
Motor connection |
|
Flat connector for M10 screw |
Flat connector for M10 screw |
PE connection |
|
M6 screw |
M6 screw |
Cable length, max. between output reactor and motor |
|
|
|
|
m (ft) |
300 (984) |
300 (984) |
|
m (ft) |
450 (1476) |
450 (1476) |
Dimensions |
|
|
|
|
mm (in) |
270 (10.6) |
270 (10.6) |
|
mm (in) |
248 (9.76) |
248 (9.76) |
|
mm (in) |
200 (7.87) |
200 (7.87) |
Degree of protection |
|
IP00 |
IP00 |
Weight, approx. |
kg (lb) |
25 (55.1) |
25.8 (56.9) |
Suitable for |
Type |
6SL3210-1RH28-0 . L0 |
6SL3210-1RH31-2 . L0 |
|
|
FSF |
FSF |