vertical bus. Model 2 introduced in 1983 to accommodate
present automated wiring programs and harness routing. Model 3 introduced in 1991 using flat bar vertical bus. Breakers use
MicroVersa Trip 9, RMS9, EPIC, MVT Plus, MVT PM trip units. Aluminum bus removed from design in 1996 in favor of standard
tin-plated copper bus (silver plating optional). Field convertible space compartment design added to allow empty
compartments to be modified to functioning breaker compartment without modifications to vertical bus.
1998- AKD-10 Introduced March 1998 as the successor to AKD-8. Manufactured along with AKD-8 for 1998 and 1999. Uses only
present WavePro low voltage power circuit breakers. Same dimensions as AKD-8. Only changes from AKD-8 are in the front breaker
compartment — new drawout rails, breaker door, secondary disconnects instrument panel. No need for Remote Display
for trip unit since WavePro breaker has trip unit in the escutcheon. AKD-10 can match & line-up with AKD-8 without a transition
(for indoor and outdoor construction). Same bus structure, frame, options, layouts and breaker stacking as AKD-8.
2005- Entellisys Introduced October 2005 as a new platform for low voltage switchgear. Uses non-automatic EntelliGuard
present breakers (similar to WavePro except no current sensors, no trip unit, and limited accessories). Entellisys uses redundant
components for highest reliability and maximum up-time. Redundant CPU’s perform all protection, metering, control,
and monitoring functions. Other redundant components of the system include 2 UPS’s, 2 network communication
switches for internal communication, 2 control power throwover relays, 2 control power sources (120vAC). Each breaker
cubicle is provided with an EntelliGuard Messenger, which is the interface between the CPU’s and the circuit breaker
operating mechanisms. The Messenger performs A/D and D/A conversions plus provides back-up overcurrent proteciton
for the breaker if all control power and communications are lost.
Equipment construction is the same as AKD-10 switchgear (frame, bussing, drawout cubicles, etc). Entellisys does
not replace AKD-10. Both product lines are currently being produced.
2
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-3
to change without notice
Low Voltage Power and DC Circuit Breakers
Gerapid High Speed DC Circuit Breakers
Technical Data for Rectifier Circuit Breaker Models 8007R and 10007R
Breaker type Gerapid 8007R Gerapid 1007R
Arc chute type 1x2 1x3 1x2 1x3
Rated current In/A 6,000 6,000 8,000 8,000
Rated operating voltage Ue/V 800 1,200 800 1,200
Rated insulation voltage Ui/V 2,000 2,000 2,000 2,000
120 min./A 7,200 7,200 9,600 9,600
Short time current 2 min./A 8,000 8,000 16,000 16,000
20 sec./A 12,000 12,000 24,000 24,000
Mechanical endurance ops. 10,0001 10,0001 10,0001 10,0001
Total weight approx. kg 220 220 220 220
1With regular maintenance 100,000 ops.
Figure 3. Gerapid 8007R and 10007R Rectifier CB, 1X2 Arc Chute, 800VDC
(Dimensions in mm)
Switchgear
2
2-4 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
AK and AKR Low Voltage Power Circuit Breakers
New AK and AKR low voltage power circuit breakers are available for replacement and
retrofill needs. The following circuit breakers are available:
AK Circuit Breaker
AC Voltage Rating Frame Size Short-circuit Ratings — RMS Symmetrical KA
60 Hertz Breaker Type (Amps) With Instantaneous Trip Without Instantaneous Trip
AK-25 600 22 22
600 AK-50 1600 42 42
AK-50H 1600 65 65
AK-25 600 30 22
480 AK-50 1600 50 50
AK-50H 1600 65 65
AK-25 600 42 22
240 AK-50 1600 65 50
AK-50H 1600 85 65
AKR Circuit Breaker
AC Voltage Rating Frame Size Short-circuit Ratings — RMS Symmetrical KA
50/60 Hertz Breaker Type (Amps) With Instantaneous Trip Without Instantaneous Trip
AKR-30 800 30 30
AKR-30H 800 42 42
600 AKR-50 1600 42 42
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 65 65
AKR-100 4000 85 85
AKR-30 800 30 30
AKR-30H 800 42 42
480 AKR-50 1600 50 50
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 65 65
AKR-100 4000 85 85
AKR-30 800 42 30
AKR-30H 800 50 42
240 AKR-50 1600 65 50
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 85 65
AKR-100 4000 130 85
Contact your local GE sales representative for price and delivery. Be prepared to provide full
nameplate data from your existing low voltage switchgear lineup.
AK-25 Breaker
AKR-30H Breaker
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-5
to change without notice
AK-25 Breaker with EntelliGuard? TU Trip Unit
Low Voltage Power and DC Circuit Breakers
Trip Unit Conversion Kits
EntelliGuard? TU Conversion Kits
GE offers a complete line of trip unit upgrade kits for low voltage
power circuit breakers manufactured by GE, as well as by
Westinghouse, I-T-E, and Allis-Chalmers. These conversion kits
contain everything necessary to convert an old-style electromechanical
or solid-state trip unit to today's latest electronic,
digital technology—including the addition of metering, protective
relay, waveform capture, RELT, and communication functions.
All conversion kits designed by GE are tested to ANSI C37.59
standards for each breaker type so customers have the
assurance of safe, reliable operation.
Features and Benefits–All Kits
—Kit includes everything needed in one compact package
—Full-range of interchangeable rating plugs
—Trip targets for quick identification of overload, short circuit,
and ground fault trips
—Sealable, see-through cover to prevent unauthorized access to
trip unit settings
—Portable Trip Unit Test Kits; GTUTK20 and TVRMS2
—Eliminate costly downtime due to nuisance tripping
—Improved power system coordination and protection
—Extend life and function of existing breakers and low voltage
equipment
EntelliGuard? TU Conversion Kits
—True RMS sensing with a sampling rate of 48 samples per cycle
with the ability to Waveform capture 4 cycles prior and 4 cycles
after an event
—Long Time, Short Time, and Instantaneous Standard on all trip
units. S and I switchable on ANSI breakers
—Large backlit LCD screen, view all currents on one screen
—Trip settings and trip target information stored in non-volatile
memory
—On-board lithium battery (field replaceable) for cold set-up and
reading trip targets
—Status and Event Log, view the last 10 events
—Health Status LED and Thermal Memory
—Comm port for interface with set-up software and to download
Waveform
—Optional metering, relaying, communications, ZSI - I, ground
fault (trip & alarm), and fused shaped curves
—Plug and Play with previous generation of RMS9, EPIC, MVT and
Enhanced MVT Trip Units
ProTrip? Conversion Kits
—Cost-effective upgrade with standard adjustable long time,
short time, instantaneous, and defeatable ground fault functions
—Simple-to-use rotary switches for selecting the trip unit pickup
and delay settings
—True RMS sensing with sampling rate of 48 times per cycle
per phase - accurate waveform measurements through the
11th harmonic
—Standard target module with individual LEDs for overload pickup,
overload trip, short circuit trip, ground fault trip, and target
module battery monitor
Everything You Need in One Package
ProTrip? and EntelliGuard? TU conversion kits for the breakers
listed in the following pages are shipped complete with detailed
installation instructions and everything needed for fast and easy
trip unit conversions.
—Digital solid-state trip with quick disconnect
—Direct-acting flux shift trip actuator with automatic reset
—Epoxy encapsulated high-accuracy current sensors
—Interchangeable rating plug (order separately)
—Specially designed mounting hardware and wire harnesses for
each breaker frame
Switchgear
2
2-6 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
Trip Unit Conversion Kits
EntelliGuard? TU Trip Unit
EntelliGuard? TU Conversion Kits—
Upgrade your low-voltage equipment with
electronic trip unit technology.
Normal wear and tear of aging electro-mechanical trip devices
on low-voltage circuit breakers increases susceptibility to loss of
calibration that can subsequently jeopardize electrical power
system coordination, protection and reliability.
GE has channeled its decades of circuit breaker trip system
experience into the development of the EntelliGuard? TU Trip Unit.
The EntelliGuard? TU builds on the past trip units by incorporating
advance algorithms that enable Arc Flash protection and
Selectivity at the same time.
ANSI C37.59 design verification tested to ensure safe, reliable
operation, these kits are designed to extend the life of your
mechanically sound breaker and…
—Eliminate costly downtime due to nuisance tripping. Improves
on past trip units with a Waveform Recognition Instantaneous
Algorithm
—Improve electrical power system coordination and protection
—Permit easy upgrades to communicating Power Management
Control Systems (PMCS), open Modbus RTU protocol
—Enable the implementation of RELT and Zone Selective Interlock
Instantaneous to reduce Arc Flash Energy Levels.
Standard Features
—Flexible Time Current Settings
—I
2T Long Time, Long Time Delay
—Short Time, Short Time Delay, 3 Short Time I2T Slopes
—Waveform Recognition Instantaneous
—Ammeter
—Large Backlit LCD Screen1
—Date and Time1
—Breaker Status Indication
—Universal Rating Plugs
—Status and Event Log (10 Events)
—LED Health Status Indicator1
—Set-up Software
—I/O – 1 Input and 1 Output1
—Thermal Memory, Battery Back-up
—Common Interface across all versions
Optional
—Internal/External Ground Fault Trip or Alarm with 4 curves to
select from (I2T, I4T, SGF, Definite Time Slope)1
—Switchable Ground Fault Trip / Alarm (not UL Listed)
—Fused Long Time Curves (I4T)
—Modbus Open RTU Communications1
—Waveform Capture – Enables Harmonic analysis
—Full-function Metering1
—Protective Relaying1
—Zone Selective Interlock – GF, S, I1
—RELT – Reduce Energy Let Through1
—RELT and Ground Fault Alarm Harness Kits
—Test Set GTUTK20
Test Kit – GTUTK20
Arc Flash and Selectivity at the same time
The EntelliGuard? TU Trip Unit offers optimum circuit protection
and optimum system reliability simultaneously with little or no
compromise to either of these critical functions. Reliability and arc
flash protection, in one package, at the same time, all the time.
Algorithms enabling arc flash protection and selectivity
—RELT – Reduced Energy Let Through
—Zone Selective Interlocking – Instantaneous (ZSI-I)
—Waveform Recognition Instantaneous – Coordinate with Current
Limiting Devices and reduces Nuisance Trips
—Flexible Time Current Curves – Create the shape you need
Reliability – Health Status
—Non-volatile memory with continuous self-testing microprocessor
—Health Status LED indicates Normal Operation, Errors, Pick-up, Trip
—External Power Not Required with Long Life Lithium Battery
—Positive setpoint recognition, values flash until saved
Plug and Play
—Same Form, Fit, Function as the popular MicroVersaTrip? Trip
Unit. Easily upgrade an existing converted breaker1
Optional Full-function metering including
—current (Amps, kAmps)
—voltage (Ph-Ph, Ph-N)
—energy (kWh, MWh, GWh)
—real power (kW, MW)
—total power (kVA, MVA)
—frequency (Hz)
—demand (avg. kW, MW) and peak demand
Optional protective relaying functions include
—undervoltage
—overvoltage
—voltage unbalance
—current unbalance
—power reversal
—power direction setup
1Note: Some options require 24VDC, additional hardware to enable Metering,
Relaying, RELT, ZSI, Modbus to be added to the Breaker, Equipment Cubicle,
and Equipment Sections.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-7
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For GE Circuit Breakers
Product Number Structure
PK115 3 F 01 08 D
Breaker
AK-1-15
AK-15
AK-1-25
AK-25
AKU-25
AK-1-50
AK-50
AKU-502
AKT-50
AKS-50
AKSU-502
AKST-50
AK-753
AK-1003
Wiring
3 Wire-3
4 Wire-4
Sensor Type
Fixed CTs-F
For converting AK-2 version breakers and newer, not applicable for AK-1 or AKR
Breakers equipped with older style open fuse lockout devices (OFLO), must be
retrofitted with newer style OFLO device prior to conversion process.
Order replacement OFLO kits as follows: AKU-50 - order OFLO kit #121C287OG2,
AK-75 - order OFLO kit #121C287OG3, AK-100 - order OFLO kit #121C287OG4
Contact the factory for stationary breaker applications
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
and Switchable Ground Fault (off)
Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
225A- 02
600A- 06
800A- 08
1600A- 16
2000A- 20
3000A- 30
4000A- 40
Sensor Rating Selection
Frame Breaker Product Numbers Sensors
PK115
PKO151
PK125
PKO753
PKO501
PK150
PKO251
PKO103
225 AK-1-15, AK-15 150A, 225A
600 AK-1-25, AK-25, AKU-25 150A, 225A, 600A
AK-1-50, AK-50, AKU-50,
AKS-50, AKSU-50
2000 AKT-50, AKST-50 2000A
3000 AK-75 3000A
4000 AK-100 4000A
1600 800A, 1600A
1
2
3
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 AK-1-15 3 Wire 150A PK115D3F0108 纬轩机电2550.00
225 AK-1-15 3 Wire 225A PK115D3F0208 纬轩机电2550.00
225 AK-1-15 4 Wire 150A PK115D4F0108 纬轩机电2775.00
225 AK-1-15 4 Wire 225A PK115D4F0208 纬轩机电2775.00
225 AK-15 3 Wire 150A PKO15D3F0108 纬轩机电2550.00
225 AK-15 3 Wire 225A PKO15D3F0208 纬轩机电2550.00
225 AK-15 4 Wire 150A PKO15D4F0108 纬轩机电2775.00
225 AK-15 4 Wire 225A PKO15D4F0208 纬轩机电2775.00
600 AK-1-25 3 Wire 150A PK125D3F0108 纬轩机电2550.00
600 AK-1-25 3 Wire 225A PK125D3F0208 纬轩机电2550.00
600 AK-1-25 3 Wire 600A PK125D3F0608 纬轩机电2550.00
600 AK-1-25 4 Wire 150A PK125D4F0108 纬轩机电2775.00
600 AK-1-25 4 Wire 225A PK125D4F0208 纬轩机电2775.00
600 AK-1-25 4 Wire 600A PK125D4F0608 纬轩机电2775.00
600 AK-25, AKU-25 3 Wire 150A PKO25D3F0108 纬轩机电2550.00
600 AK-25, AKU-25 3 Wire 225A PKO25D3F0208 纬轩机电2550.00
600 AK-25, AKU-25 3 Wire 600A PKO25D3F0608 纬轩机电2550.00
600 AK-25, AKU-25 4 Wire 150A PKO25D4F0108 纬轩机电2775.00
600 AK-25, AKU-25 4 Wire 225A PKO25D4F0208 纬轩机电2775.00
600 AK-25, AKU-25 4 Wire 600A PKO25D4F0608 纬轩机电2775.00
1600 AK-1-50 3 Wire 800A PK150D3F0808 纬轩机电2800.00
1600 AK-1-50 3 Wire 1600A PK150D3F1608 纬轩机电2800.00
1600 AK-1-50 4 Wire 800A PK150D4F0808 纬轩机电3025.00
1600 AK-1-50 4 Wire 1600A PK150D4F1608 纬轩机电3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 800A PKO50D3F0808 纬轩机电2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 1600A PKO50D3F1608 纬轩机电2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 2000A PKO50D3F2008 纬轩机电2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 800A PKO50D4F0808 纬轩机电3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 1600A PKO50D4F1608 纬轩机电3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 2000A PKO50D4F2008 纬轩机电3025.00
3000 AK-75 3 Wire 3000A PKO75D3F3008 纬轩机电2800.00
3000 AK-75 4 Wire 3000A PKO75D4F3008 纬轩机电3025.00
4000 AK-100 3 Wire 4000A PKO10D3F4008 纬轩机电3050.00
4000 AK-100 4 Wire 4000A PKO10D4F4008 纬轩机电3275.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separately. See page 2-11.
Switchgear
2
2-8 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *I-T-E Circuit Breakers
Product Number Structure
PIK22 D 3 F 02 08
Breaker
K225
K600
KD0N600
K800
KD0N800
K1600 (black)
KD0N1600 (black)
K1600 (red)
KD0N1600 (red)
Wiring
3 Wire-3
4 Wire-4
Sensor Type
Fixed CTs-F
Applicable to breakers originally equipped with either electro-mechanical
trip devices or with solid state trip devices ("S" version breakers).
Only applicable to breakers originally equipped with rectangular shaped
primary disconnect assemblies.
Only applicable to breakers originally equipped with circular shaped
primary disconnect assemblies.
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
and Switchable Ground Fault (off)
Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
225A- 02
400A- 04
600A- 06
800A- 08
1600A- 16
Sensor Rating Selection
Frame Breaker Product Numbers Sensors
PIK221
PIK601
PIK801
PIK1B1
PIK161,2
PIKN1,3
225 K225 150A, 225A
600 K600, KD0N600 150A, 225A, 600A
800 K800, KD0N800 150A, 400A, 800A
K1600 (black),
1600 KD0N1600 (black), 800A, 1600A
K1600 (red), KD0N1600 (red)
1
2
3
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 K225 3 Wire 150A PIK22D3F0108 纬轩机电2450.00
225 K225 3 Wire 225A PIK22D3F0208 纬轩机电2450.00
225 K225 4 Wire 150A PIK22D4F0108 纬轩机电2675.00
225 K225 4 Wire 225A PIK22D4F0208 纬轩机电2675.00
600 K600, KDON600 3 Wire 150A PIK60D3F0108 纬轩机电2350.00
600 K600, KDON600 3 Wire 225A PIK60D3F0208 纬轩机电2350.00
600 K600, KDON600 3 Wire 600A PIK60D3F0608 纬轩机电2350.00
600 K600, KDON600 4 Wire 150A PIK60D4F0108 纬轩机电2575.00
600 K600, KDON600 4 Wire 225A PIK60D4F0208 纬轩机电2575.00
600 K600, KDON600 4 Wire 600A PIK60D4F0608 纬轩机电2575.00
800 K800, KDON800 3 Wire 150A PIK80D3F0108 纬轩机电2350.00
800 K800, KDON800 3 Wire 400A PIK80D3F0408 纬轩机电2350.00
800 K800, KDON800 3 Wire 800A PIK80D3F0808 纬轩机电2350.00
800 K800, KDON800 4 Wire 150A PIK80D4F0108 纬轩机电2575.00
800 K800, KDON800 4 Wire 400A PIK80D4F0408 纬轩机电2575.00
800 K800, KDON800 4 Wire 800A PIK80D4F0808 纬轩机电2575.00
1600 K1600 (black), KDON1600 (black) 3 Wire 800A PIK1BD3F0808 纬轩机电2700.00
1600 K1600 (black), KDON1600 (black) 3 Wire 1600A PIK1BD3F1608 纬轩机电2700.00
1600 K1600 (black), KDON1600 (black) 4 Wire 800A PIK1BD4F0808 纬轩机电2925.00
1600 K1600 (black), KDON1600 (black) 4 Wire 1600A PIK1BD4F1608 纬轩机电2925.00
1600 K1600 (red) 3 Wire 800A PIK16D3F0808 纬轩机电2700.00
1600 K1600 (red) 3 Wire 1600A PIK16D3F1608 纬轩机电2700.00
1600 K1600 (red) 4 Wire 800A PIK16D4F0808 纬轩机电2925.00
1600 K1600 (red) 4 Wire 1600A PIK16D4F1608 纬轩机电2925.00
1600 KDON1600 (red) 3 Wire 800A PIKN1D3F0808 纬轩机电2700.00
1600 KDON1600 (red) 3 Wire 1600A PIKN1D3F1608 纬轩机电2700.00
1600 KDON1600 (red) 4 Wire 800A PIKN1D4F0808 纬轩机电2925.00
1600 KDON1600 (red) 4 Wire 1600A PIKN1D4F1608 纬轩机电2925.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separately. See page 2-11.
*I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-9
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *Allis-Chalmers Circuit Breakers
Product Number Structure
PSL6B 3 F 02 08 D
Breaker
LA-600 (blue)
LAF-600 (blue)
LA-600 (gold)
LAF-600 (gold)
LA-800 (gold)
LAF-800 (gold)
LA-1600 (blue)
LAF-1600 (blue)
LA-1600 (gold)
LAF-1600 (gold)
Wiring
3 Wire-3
4 Wire-4
Sensor Type
Fixed CTs-F
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
and Switchable Ground Fault (off)
Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
225A- 02
400A- 04
600A- 06
800A- 08
1600A- 16
Sensor Rating Selection
Frame Breaker Product Numbers Sensors
LA-600 (blue), LAF-600 (blue)
LA-600 (gold), LAF-600 (gold)
LA-800 (gold), LAF-800 (gold)
LA-1600 (blue), LAF-1600 (blue)
LA-1600 (gold), LAF-1600 (gold)
PSL6B
PSL6G
PSL8O
PSL1B
PSL1G
600
800
1600
150A, 225A, 600A
150A, 400A, 800A
800A, 1600A
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
600 LA-600 (blue), LAF-600 (blue) 3 Wire 150A PSL6BD3F0108 纬轩机电2350.00
600 LA-600 (blue), LAF-600 (blue) 3 Wire 225A PSL6BD3F0208 纬轩机电2350.00
600 LA-600 (blue), LAF-600 (blue) 3 Wire 600A PSL6BD3F0608 纬轩机电2350.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 150A PSL6BD4F0108 纬轩机电2575.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 225A PSL6BD4F0208 纬轩机电2575.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 600A PSL6BD4F0608 纬轩机电2575.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 150A PSL6GD3F0108 纬轩机电2350.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 225A PSL6GD3F0208 纬轩机电2350.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 600A PSL6GD3F0608 纬轩机电2350.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 150A PSL6GD4F0108 纬轩机电2575.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 225A PSL6GD4F0208 纬轩机电2575.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 600A PSL6GD4F0608 纬轩机电2575.00
800 LA-800 (gold) 3 Wire 150A PSL80D3F0108 纬轩机电2500.00
800 LA-800 (gold) 3 Wire 400A PSL80D3F0408 纬轩机电2500.00
800 LA-800 (gold) 3 Wire 800A PSL80D3F0808 纬轩机电2500.00
800 LA-800 (gold) 4 Wire 150A PSL80D4F0108 纬轩机电2725.00
800 LA-800 (gold) 4 Wire 400A PSL80D4F0408 纬轩机电2725.00
800 LA-800 (gold) 4 Wire 800A PSL80D4F0808 纬轩机电2725.00
1600 LA-1600 (blue), LAF-1600 (blue) 3 Wire 800A PSL1BD3F0808 纬轩机电2700.00
1600 LA-1600 (blue), LAF-1600 (blue) 3 Wire 1600A PSL1BD3F1608 纬轩机电2700.00
1600 LA-1600 (blue), LAF-1600 (blue) 4 Wire 800A PSL1BD4F0808 纬轩机电2925.00
1600 LA-1600 (blue), LAF-1600 (blue) 4 Wire 1600A PSL1BD4F1608 纬轩机电2925.00
1600 LA-1600 (gold), LAF-1600 (gold) 3 Wire 800A PSL1GD3F0808 纬轩机电2700.00
1600 LA-1600 (gold), LAF-1600 (gold) 3 Wire 1600A PSL1GD3F1608 纬轩机电2700.00
1600 LA-1600 (gold), LAF-1600 (gold) 4 Wire 800A PSL1GD4F0808 纬轩机电2925.00
1600 LA-1600 (gold), LAF-1600 (gold) 4 Wire 1600A PSL1GD4F1608 纬轩机电2925.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separately. See page 2-11.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
Switchgear
2
2-10 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *Westinghouse Circuit Breakers
Product Number Structure
PDB15 3 F 02 08 D
Breaker
DB15, DBL15- PDB15
DB25, DBL25- PDB25
DB50, DBL50- PDB50
DB75- PDB75
DB100- PDB10
Wiring
3 Wire-3
4 Wire-4
Sensor Type
Fixed CTs-F
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
and Switchable Ground Fault (off)
Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
225A- 02
600A- 06
800A- 08
1600A- 16
3000A- 30
4000A- 40
Sensor Rating Selection
Frame Breaker Product Numbers Sensors
225 DB15, DBL15 150A, 225A
600 DB25, DBL25 225A, 600A
1600 DB50, DBL50 800A,1600A
3000 DB75 3000A
4000 DB100 4000A
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 DB15, DBL15 3 Wire 150A PDB15D3F0108 纬轩机电2250.00
225 DB15, DBL15 3 Wire 225A PDB15D3F0208 纬轩机电2250.00
225 DB15, DBL15 4 Wire 150A PDB15D4F0108 纬轩机电2475.00
225 DB15, DBL15 4 Wire 225A PDB15D4F0208 纬轩机电2475.00
600 DB25, DBL25 3 Wire 150A PDB25D3F0108 纬轩机电2350.00
600 DB25, DBL25 3 Wire 225A PDB25D3F0208 纬轩机电2350.00
600 DB25, DBL25 3 Wire 600A PDB25D3F0608 纬轩机电2350.00
600 DB25, DBL25 4 Wire 150A PDB25D4F0108 纬轩机电2575.00
600 DB25, DBL25 4 Wire 225A PDB25D4F0208 纬轩机电2575.00
600 DB25, DBL25 4 Wire 600A PDB25D4F0608 纬轩机电2575.00
1600 DB50, DBL50 3 Wire 800A PDB50D3F0808 纬轩机电2350.00
1600 DB50, DBL50 3 Wire 1600A PDB50D3F1608 纬轩机电2350.00
1600 DB50, DBL50 4 Wire 800A PDB50D4F0808 纬轩机电2575.00
1600 DB50, DBL50 4 Wire 1600A PDB50D4F1608 纬轩机电2575.00
3000 DB75 3 Wire 3000A PDB75D3F3008 纬轩机电2600.00
3000 DB75 4 Wire 3000A PDB75D4F3008 纬轩机电2825.00
4000 DB100 3 Wire 4000A PDB10D3F4008 纬轩机电2850.00
4000 DB100 4 Wire 4000A PDB10D4F4008 纬轩机电3075.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separately. See page 2-11.
*Westinghouse is a trademark of Westinghouse Electric Corporation.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-11
to change without notice
*I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
*Westinghouse is a trademark of Westinghouse Electric Corporation.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
Low Voltage Power and DC Circuit Breakers
ProTrip? Rating Plugs
ProTrip? conversion kits come standard with a rating plug that
matches the current sensor. For rating plugs with different values,
price and order separately.
Rating Plug
Reference Publications
ProTrip? Trip Unit Conversion Kits for
GE Power Circuit Breakers - Fact Sheet DET-228
ProTrip? Trip Unit Conversion Kits for
*Westinghouse Power Circuit Breakers - Fact Sheet DET-230
ProTrip? Trip Unit Conversion Kits for
*Allis-Chalmers Power Circuit Breakers - Fact Sheet DET-231
ProTrip? Trip Unit Conversion Kits for
*I-T-E Power Circuit Breakers - Fact Sheet DET-229
Rating Plugs
List Price
Frame Size (Amps) Sensor Rating (Amps) Current Rating (Amps) Current Range (Amps) Product Number GO-104P
225|600|800 150 80 40-88 PT1C80GFD 纬轩机电149.00
225|600|800 150 100 50-110 PT1C100GFD 纬轩机电149.00
225|600|800 150 125 63-138 PT1C125GFD 纬轩机电149.00
225|600|800 150 150 75-165 PT1C150GFD1 纬轩机电149.00
225|600|800 225 150 75-165 PT225C150GFD 纬轩机电149.00
225|600|800 225 225 113-248 PT225C225GFD1 纬轩机电149.00
600 600 300 150-330 PT6C300GFD 纬轩机电149.00
600 600 400 200-440 PT6C400GFD 纬轩机电149.00
600 600 450 225-495 PT6C450GFD 纬轩机电149.00
600 600 500 250-550 PT6C500GFD 纬轩机电149.00
600 600 600 300-660 PT6C600GFD1 纬轩机电149.00
800 400 200 100-220 PT4C200GFD 纬轩机电149.00
800 400 225 113-248 PT4C225GFD 纬轩机电149.00
800 400 250 125-275 PT4C250GFD 纬轩机电149.00
800 400 300 150-330 PT4C300GFD 纬轩机电149.00
800 400 400 200-440 PT4C400GFD1 纬轩机电149.00
800|1600 800 400 200-440 PT8C400GFD 纬轩机电149.00
800|1600 800 450 225-495 PT8C450GFD 纬轩机电149.00
800|1600 800 500 250-550 PT8C500GFD 纬轩机电149.00
800|1600 800 600 300-660 PT8C600GFD 纬轩机电149.00
800|1600 800 700 350-770 PT8C700GFD 纬轩机电149.00
800|1600 800 800 400-880 PT8C800GFD1 纬轩机电149.00
1600 1600 800 400-880 PT16C800GFD 纬轩机电149.00
1600 1600 1000 500-1100 PT16C1000GFD 纬轩机电149.00
1600 1600 1100 550-1210 PT16C1100GFD 纬轩机电149.00
1600 1600 1200 600-1320 PT16C1200GFD 纬轩机电149.00
1600 1600 1600 800-1760 PT16C1600GFD 纬轩机电149.00
2000 2000 1000 500-1100 PT20C1000GFD 纬轩机电149.00
2000 2000 1200 600-1320 PT20C1200GFD 纬轩机电149.00
2000 2000 1500 750-1650 PT20C1500GFD 纬轩机电149.00
2000 2000 1600 800-1760 PT20C1600GFD 纬轩机电149.00
2000 2000 2000 1000-2200 PT20C2000GFD 纬轩机电149.00
3000 3000 1200 600-1320 PT30C1200GFD 纬轩机电149.00
3000 3000 1600 800-1760 PT30C1600GFD 纬轩机电149.00
3000 3000 2000 1000-2200 PT30C2000GFD 纬轩机电149.00
3000 3000 2500 1250-2750 PT30C2500GFD 纬轩机电149.00
3000 3000 3000 1500-3300 PT30C3000GFD1 纬轩机电149.00
4000 4000 1600 800-1760 PT40C1600GFD 纬轩机电149.00
4000 4000 2000 1000-2200 PT40C2000GFD 纬轩机电149.00
4000 4000 2500 1250-2750 PT40C2500GFD 纬轩机电149.00
4000 4000 3000 1500-3300 PT40C3000GFD 纬轩机电149.00
4000 4000 3600 1800-3960 PT40C3600GFD 纬轩机电149.00
4000 4000 4000 2000-4000 PT40C4000GFD1 纬轩机电149.00
Rating Plug furnished with conversion kit.
Note: Long Time pickup range is 0.5-1.1 times the rating plug value. 1.1 setting allows the breaker to carry 100% of the rating plug current value, not to exceed the
continuous current (frame) rating of the breaker.
Switchgear
2
2-12 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kits Selection Guide
Sensor Rating Selection
AKO25 C 3 F 06 04 A
Breaker
AK-1-15 = AK115
AK-15 = AKO151
AK-1-25 = AK125
AK-25
AKU-25 = AKO251
AKR-30
AKR-30H = AKR30
AKRU-30
AKR-30S
AKRU-30S = AKR3S2
AK-1-50 = AK150
AK-50
AKU-503
AKT-50 = AKO501
AKS-50
AKSU-503
AKST-50
AKR-50
AKR-50H
AKRU-50
AKRT-50
AKRT-50H = AKR504
AKJ-50
AKJ-50H
AKJT-50
AKJT-50H
AK-753 = AKO755
AKR-75 = AKR755
AK-1003 = AKO105
AKR-100 = AKR105
AKW-100 = AKW105
Breaker
DB-15 = ADB15
DK-15 = ADK159
DB-25
DBL-25 = ADB25
DK-25 = ADK259
DS-206
DSL-206 = ADS06
DA-50 = ADA509
DB-50
DBL-50 = ADB50
DS-416 = ADS16 DSL-416
DS-420 = ADS20
DS-532 = ADS539
DA-75 = ADA759
DB-75 = ADB75
DS-632 = ADS32
DA-100 = ADA109
DB-100 = ADB10
DS-840 = ADS409
GE ***Westinghouse25 *Allis-Chalmers25 **I-T-E25
Breaker
LA = ASL259
LA-25A = ASL2A9
LA-600(Blue) = ASL6B17,18
LAF-600(Blue) = ASL6B17,18,19
LA-600(Gold) = ASL6G18,20
LAF-600(Gold) = ASL6G18,19,20
LA-50(800A) = ASL589,21
LA-800 = ASL8018,20
LAF-800 = ASL8018,19,20
RL-800 = ASR80
RLX-800 = ASR80
RLE-800 = ASR80
LA-50(1600A) = ASL519,22
LA-50(1600A) = ASL529,23
LA-1600(Blue) = ASL1B17,18
LAF-1600(Blue) = ASL1B17,18,19
LA-1600(Gold) = ASL1G18,20
LAF-1600(Gold) = ASL1G18,19,20
RL-1600 = ASR16
RLX-1600 = ASR16
RLE-1600 = ASR16
RL-2000 = ASR09
LA-75 = ASL759
LA-3000 = ASL309,18
LA-3200(Blue) = ASL3B9,
17,18
LA-3200(Gold) = ASL3G9,18,20
RL-3200 = ASR329
LA-4000(Blue) = ASL4B9,17,18
LA-4000(Gold) = ASL4G9,18,20
RL-4000 = ASR409
Breaker
KA = AIKA210,11
K-225 = AIK22
KB (metal) = AIKBM12
KB (slate drawout) = AIKBS12
KB (slate stationary) = AIKBX12
K-600
KDON-600 = AIK60
KC (800A) = AIKC810,12,14
K-800 = AIK80 KDON-800
KC (1600A) = AIKC110,12,13
K-1600 (red) = AIK1615
K-1600 (black) = AIK1B15
KDON-1600 (black)
KDON-1600 (red) = AIKN1
K-2000 = AIK20
KD = AIKD316
K-3000 = AIK30
KE = AIKE416
LG = AIKG49
K-4000 = AIK40
Blue = Blue-gray breaker with plastic escutcheon
Gold = Gold breaker with metal escutcheon
Frame Sensors
Breaker Catalog Numbers
GE *Allis-Chalmers **I-T-E ***Westinghouse
225 150 AK-1-15, AK-15 Sensor rating not available. KA, KA-225 DB-15, DK-15 225
600
150
AK-1-25, AK-25, AKU-25
— — —
225 LA-25, LA-25A, LA-600,
LAF-600 KB, K-600, KDON-600 DB-25, DBL-25, DK-25 600
800
150 AKR-30, AKR-30H, AKRU-30,
AKR-30S, AKRU-30S
LA-50 (800A Version), LA-800, LAF-800,
RL-800, RLE-800, RLX-800
KC (800A Version),
K-800, KDON-800 400 DS-206, DSL-206
800
1600
800 AK-1-50, AK-50, AKU-50, AKS-50,
AKSU-50, AKR-50, AKR-50H,
AKRU-50, AKJ-50, AKJ-50H
LA-50 (1600A Version),
LA-1600, LAF-1600, RL-1600,
RLE-1600, RLX-1600
KC (1600A Version),
K-1600, KDON-1600
DA-50, DB-50, DBL-50,
DS-416, DSL-416 1600
2000 2000 AKT-50, AKST-50, AKRT-50,
AKRT-50H, AKJT-50, AKJT-50H RL-2000 K-2000 DS-420
3000 3000 AK-75 LA-75, LA-3000 KD, K-3000 DA-75, DB-75
3200 3200 AKR-75 LA-3200, RL-3200 — DS-632
4000 4000 AK-100, AKR-100, AKW-100 LA-4000, RL-4000 KE, LG, K-4000 DA-100, DB-100, DS-840
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
**I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
***Westinghouse is a trademark of Westinghouse Electric Corporation.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-13
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kits Selection Guide
1For converting AK-2 version breakers and newer, not applicable for AK-1 or AKR.
2AKR30S Instantaneous Is Non-Switchable and the Non-Switchable High Range
Instantaneous max is 22KA. LSH and LSHG Are Only Available on AKR30S.
3Breakers equipped with older style open fuse lockout devices (OFLO), must be
retrofitted with newer style OFLO device prior to conversion process. Order
replacement OFLO kits as follows: AKU-50 - order OFLO Kit #121C2870G2,
AK-75 - order OFLO kit #121C2870G3, AK-100 - order OFLO kit #121C2870G4.
4Not applicable for converting breakers equipped with Power Sensor - contact
factory.
5Contact the factory for stationary breaker applications.
6Only applicable to trip units with ground fault.
7Available only for MicroVersaTrip RMS-9 type AKR breakers equipped with fixed
current sensors.
8Not available on AK-75 breaker frames.
9Contact factory for availability.
10Not applicable for slate version breakers.
11Left pole accessories must be removed or relocated.
12Right pole accessories must be removed or relocated.
131600-amp version of the KC breaker.
14800-amp version of the KC breaker.
15Order for red or black insulator as applicable.
16Not applicable to fixed mounted breakers.
17Only applicable for blue-gray color version breakers.
18Applicable to both “A” and “B” version breakers.
19Applicable to both nameplated versions of integral fused breakers
(i.e., LA-600F and LAF-600).
20Only applicable for gold color version breakers.
21800-amp version of the LA-50 breaker.
22Only applicable for the 1600-amp, 6-pole primary disconnect version of
the LA-50 breaker.
23Only applicable for 1600-amp, 12 pole primary disconnect version of the
LA-50 breaker.
24Requires 24VDC control power.
25Existing Allis-Chalmers, I-T-E and Westinghouse bell alarms will not work
with EntelliGuard TU..
Model
C = Generation
Wiring
3 Wire = 3
4 Wire6 = 4
Sensor Type
F = Fixed CTs
Sensor Ratings
150A = 01
225A = 02
400A = 04
600A = 06
800A = 08
1600A = 16
2000A = 20
3000A = 30
3200A8 = 32
4000A = 40
150A No CTs7 = XA
400A No CTs7 = XC
800A No CTs7 = XE
1600A No CTs7 = XF
2000A No CTs7 = XG
3200A No CTs7,8 = XI
4000A No CTs7 = XJ
Trip Functions
04 = LSI2
05 = LSIG2
09 = LSIGDA
11 = LSH2
12 = LSHG2
Adv. Options
A = Ammeter
B = Ammeter + RELT24
C = Advanced Metering, Relaying,
Waveform Capture, Modbus Comm,
RELT24
Trip Unit Functions
LSI = Long Time, Short Time (Switchable),
& Instantaneous (Switchable)
LSIG = LSI & Ground Fault Trip
LSIGDA = LSIG with Switchable Ground
Fault Alarm (not UL Listed)
LSH = Long Time, Short Time (Switchable),
High Range Instantaneous
(Non-Switchable) Up to 22KA
(AKR30S Only)2
LSHG = LSH & Ground Fault Trip
(AKR30S Only)2
ZSI – Instantaneous is available.
Contact factory.
RELT (Reduced Energy Let Through) –
Order RELT Switch Kit GTURSK separately
Kits Without Sensors
For kits ordered without sensors, deduct 纬轩机电200.00 from the list price of
the kit with sensors. Please refer to the sensor rating column above for
the appropriate “X” sensor code.
Zone Selective Interlock
For Zone Selective Interlock (ZSI) Short Time, Ground Fault and
Instantaneous, add 纬轩机电550.00 to the list price. (Also requires purchase of
ZSI module TIM1 [120 VAC control voltage], list price 纬轩机电402.00, GO-245B.)
Reference Publications
EntelliGuard? TU Conversion Kit Brochure DET-722
EntelliGuard? TU Conversion Kit Supplemental Instructions DEH-3456
EntelliGuard? TU Trip Unit Installation/Instruction Manual DEH-4567
EntelliGuard? TU Test Set - GTUTK20 DEH-4568A
GE AK-1-15, AK-1-25 GEH-6466
GE AK-1-50 DEH-40027
GE AK-15, AK, AKU-25, AKR-30S, AKRU-30S GEH-5967
GE AKR-30,30H, AKRU-30, AKR-50, AKJ-50 Series GEH-5966
GE AK-100, AK,U,T,S,SU,ST-50, AK-75 GEH-5965
GE AKR-100, AKR-75, AKW-100 GEH-5964
Westinghouse DB-15 GEH-6318
Westinghouse DB-25, DBL-25 (225A), DB-50, DBL-50 GEH-6319
Westinghouse DS-206, DSL-206, DS416, DSL-416, DS-420, DS-632 DEH-023
Westinghouse DB-100 (4000A), DB-75 (3000A) GEH-6320
ITE K-1600 (red), K, KDON-1600 Black, K-2000, K-225, K-600,
KDON-600, K-800, KDON-800, KDON-1600 (red) GEH-6294
ITE KC (1600A), KC (800A) GEH-6433
ITE KA GEH-6293
ITE KB (Metal), KB (Slate Drawout), KB (Slate Fixed) GEH-6295
ITE K-3000, K-4000 DEH-133
ITE KD-3000, KE-4000 DEH-40019
Allis Chalmers LA, LAF - 1600 (BLUE), LA, LAF-600 (BLUE) DEH-40008
Allis Chalmers LA, LAF - 1600 (GOLD), LA, LAF-600 (GOLD), LA, LAF-800,
RL, RLX, RLE-1600 & 800 DEH-40009A
Note: Conversion Kit Pricing tables are located on pages 2-14
through 2-16.
Switchgear
2
2-14 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kits Selection Guide
For GE Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 3-Wire, List Price, GO-104G
LSI1 (04) LSIG1 (05) LSIGDA (09)
Breaker Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 AK115
AKO15
600 AK125 纬轩机电2520.00 纬轩机电2820.00 纬轩机电4920.00 纬轩机电3000.00 纬轩机电3300.00 纬轩机电5400.00 纬轩机电3620.00 纬轩机电3920.00 纬轩机电6020.00
AKO25
800 AKR30 纬轩机电2620.00 纬轩机电2920.00 纬轩机电5040.00 纬轩机电3100.00 纬轩机电3400.00 纬轩机电5520.00 纬轩机电3720.00 纬轩机电4020.00 纬轩机电6140.00
AKR3S1 ———
AK150
1600 AKO50 纬轩机电2620.00 纬轩机电2920.00 纬轩机电5040.00 纬轩机电3100.00 纬轩机电3400.00 纬轩机电5520.00 纬轩机电3720.00 纬轩机电4020.00 纬轩机电6140.00
AKR50
AK150
2000 AKO50
AKR50
3000 AKO75
3200 AKR75 纬轩机电2720.00 纬轩机电3020.00 纬轩机电5140.00 纬轩机电3200.00 纬轩机电3500.00 纬轩机电5620.00 纬轩机电3820.00 纬轩机电4120.00 纬轩机电6240.00
AKO10
4000 AKR10
AKW10
1For AK30S breakers (AKR3S), LSH and LSHG List Pricing is the same as LSI and LSIG, respectively.
For GE Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 4-Wire, List Price, GO-104G
LSI LSIG1 (04) LSIGDA (09)
Breaker Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 AK115
AKO15
600 AK125 — — — 纬轩机电3275.00 纬轩机电3575.00 纬轩机电5675.00 纬轩机电3895.00 纬轩机电4195.00 纬轩机电6295.00
AKO25
800 AKR30 — — — 纬轩机电3375.00 纬轩机电3675.00 纬轩机电5795.00 纬轩机电3995.00 纬轩机电4295.00 纬轩机电6415.00 AKR3S1
AK150
1600 AKO50 — — — 纬轩机电3375.00 纬轩机电3675.00 纬轩机电5795.00 纬轩机电3995.00 纬轩机电4295.00 纬轩机电6415.00
AKR50
AK150
2000 AKO50
AKR50
3000 AKO75 — — — 纬轩机电3475.00 纬轩机电3775.00 纬轩机电5895.00 纬轩机电4095.00 纬轩机电4395.00 纬轩机电6515.00 3200 AKR75
AKO10
4000 AKR10
AKW10
1For AK30S breakers (AKR3S), LSH and LSHG List Pricing is the same as LSI and LSIG, respectively.
For *Allis-Chalmers Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 3-Wire, List Price, GO-104G
LSI (04) LSIG (05) LSIGDA (09)
Breaker2 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
600 ASL6B 纬轩机电2960.00 纬轩机电3260.00 纬轩机电5360.00 纬轩机电3440.00 纬轩机电3740.00 纬轩机电5840.00 纬轩机电4060.00 纬轩机电4360.00 纬轩机电6460.00 ASL6G
800 ASL80
ASR80
ASL1B 纬轩机电3060.00 纬轩机电3360.00 纬轩机电5460.00 纬轩机电3540.00 纬轩机电3840.00 纬轩机电5940.00 纬轩机电4160.00 纬轩机电4460.00 纬轩机电6560.00
1600 ASL1G
ASR16
2Contact Factory for Pricing and Availability on Breaker Models not listed.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
Pricing for EntelliGuard? TU are determined by the Frame Rating,
Breaker Model, 3 or 4 wire, Trip Functions, and Advanced Features.
(Example: Items highlighted in bold AKO25 C 3 F 06 04 A)
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-15
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kits Selection Guide
For *Allis-Chalmers Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 4-Wire, List Price, GO-104G
LSI LSIG (05) LSIGDA (09)
Breaker2 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
600 ASL6B — — — 纬轩机电3715.00 纬轩机电4015.00 纬轩机电6115.00 纬轩机电4335.00 纬轩机电4635.00 纬轩机电6735.00 ASL6G
800 ASL80
ASR80
ASL1B — — — 纬轩机电3815.00 纬轩机电4115.00 纬轩机电6215.00 纬轩机电4435.00 纬轩机电4735.00 纬轩机电6835.00
1600 ASL1G
ASR16
For **I-T-E Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 3-Wire, List Price, GO-104G
LSI (04) LSIG (05) LSIGDA (09)
Breaker2 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 AIKA2
AIK22
AIKBM
AIKBS 纬轩机电2720.00 纬轩机电3020.00 纬轩机电5140.00 纬轩机电3200.00 纬轩机电3500.00 纬轩机电5620.00 纬轩机电3820.00 纬轩机电4120.00 纬轩机电6240.00
600 AIKBX
AIK60
800 AIKC8
AIK80
AIKC1
AIK16 纬轩机电2820.00 纬轩机电3120.00 纬轩机电5240.00 纬轩机电3300.00 纬轩机电3600.00 纬轩机电5720.00 纬轩机电3920.00 纬轩机电4220.00 纬轩机电6340.00
1600 AIK1B
AIKN1
2000 AIK20 纬轩机电2920.00 纬轩机电3220.00 纬轩机电5340.00 纬轩机电3400.00 纬轩机电3700.00 纬轩机电5820.00 纬轩机电4020.00 纬轩机电4320.00 纬轩机电6440.00
3000 AIK30 纬轩机电4120.00 纬轩机电4420.00 纬轩机电6540.00 纬轩机电4600.00 纬轩机电5100.00 纬轩机电7020.00 纬轩机电5220.00 纬轩机电5520.00 纬轩机电7640.00 4000 AIK40
For **I-T-E Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 4-Wire, List Price, GO-104G
LSI LSIG (05) LSIGDA (09)
Breaker2 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 AIKA2
AIK22
AIKBM
600 AIKBS — — — 纬轩机电3475.00 纬轩机电3775.00 纬轩机电5895.00 纬轩机电4095.00 纬轩机电4395.00 纬轩机电6515.00
AIKBX
AIK60
800 AIKC8
AIK80
AIKC1
1600 AIK16 — — — 纬轩机电3575.00 纬轩机电3875.00 纬轩机电5995.00 纬轩机电4195.00 纬轩机电4495.00 纬轩机电6615.00
AIK1B
AIKN1
2000 AIK20 — — — 纬轩机电3675.00 纬轩机电3975.00 纬轩机电6095.00 纬轩机电4295.00 纬轩机电4595.00 纬轩机电6715.00
3000 AIK30
4000 AIKE4 — — — 纬轩机电4875.00 纬轩机电5375.00 纬轩机电7295.00 纬轩机电5495.00 纬轩机电5795.00 纬轩机电7915.00
AIK40
2Contact Factory for Pricing and Availability on Breaker Models not listed.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
**I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
Switchgear
2
2-16 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kits Selection Guide
For *Westinghouse Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 3-Wire, List Price, GO-104
LSI (04) LSIG (05) LSIGDA (09)
Breaker1 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 ADB15 纬轩机电2520.00 纬轩机电2820.00 纬轩机电4920.00 纬轩机电3000.00 纬轩机电3300.00 纬轩机电5400.00 纬轩机电3620.00 纬轩机电3920.00 纬轩机电6020.00 600 ADB25
800 ADS06
1600 ADB50 纬轩机电3060.00 纬轩机电3360.00 纬轩机电5460.00 纬轩机电3540.00 纬轩机电3840.00 纬轩机电5940.00 纬轩机电4160.00 纬轩机电4460.00 纬轩机电6560.00
ADS16
2000 ADS20
3000 ADB75 纬轩机电3260.00 纬轩机电3560.00 纬轩机电5660.00 纬轩机电3740.00 纬轩机电4040.00 纬轩机电6140.00 纬轩机电4360.00 纬轩机电4660.00 纬轩机电6760.00 3200 ADS32
4000 ADB10
For *Westinghouse Power Circuit Breakers
EntelliGuard? TU Trip Unit Conversion Kits for 3-Phase, 4-Wire, List Price, GO-104G
LSI LSIG (05) LSIGDA (09)
Breaker1 Ammeter All Advanced Ammeter All Advanced Ammeter All Advanced
Frame Amps Model Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C) Ammeter (A) + RELT (B) Options (C)
225 ADB15 — — — 纬轩机电3275.00 纬轩机电3575.00 纬轩机电5675.00 纬轩机电3895.00 纬轩机电4195.00 纬轩机电6295.00 600 ADB25
800 ADS06
1600 ADB50 — — — 纬轩机电3815.00 纬轩机电4115.00 纬轩机电6215.00 纬轩机电4435.00 纬轩机电4735.00 纬轩机电6835.00
ADS16
2000 ADS20
3000 ADB75 — — — 纬轩机电4015.00 纬轩机电4315.00 纬轩机电6415.00 纬轩机电4635.00 纬轩机电4935.00 纬轩机电7035.00 3200 ADS32
4000 ADB10
1Contact Factory for Pricing and Availability on Breaker Models not listed.
*Westinghouse is a trademark of Westinghouse Electric Corporation.
EntelliGuard? TU Trip Rating Plug Specifications
May Be Used With
Trip Plug Plug Minimum Maximum List Price
Product Number Rating Sensor Sensor GO-329R
GTP0060U0101 60A2 150A4 150A4 纬轩机电130.00
GTP0080U0101 80A2 150A4 150A5 纬轩机电130.00
GTP0100U0103 100A3 150A4 225A5 纬轩机电130.00
GTP0125U0103 125A2 150A4 225A5 纬轩机电130.00
GTP0150U0104 150A 150A4 400A 纬轩机电130.00
GTP0200U0204 200A 200A5 400A 纬轩机电130.00
GTP0225U0306 225A 225A 600A 纬轩机电130.00
GTP0250U0407 250A 400A 630A6 纬轩机电130.00
GTP0300U0408 300A 400A 800A 纬轩机电130.00
GTP0350U0408 350A 400A 800A 纬轩机电130.00
GTP0400U0410 400A 400A 1000A 纬轩机电130.00
GTP0450U0612 450A 600A 1200A 纬轩机电130.00
GTP0500U0613 500A 600A 1250A6 纬轩机电130.00
GTP0600U0616 600A 600A 1600A 纬轩机电130.00
GTP0700U0816 700A 800A 1600A 纬轩机电130.00
GTP0750U0820 750A 800A 2000A 纬轩机电130.00
GTP0800U0820 800A 800A 2000A 纬轩机电130.00
GTP0900U1020 900A 1000A 2000A 纬轩机电130.00
GTP1000U1025 1000A 1000A 2500A 纬轩机电130.00
GTP1100U1225 1100A 1200A 2500A 纬轩机电130.00
GTP1200U1232 1200A 1200A 3200A 纬轩机电130.00
GTP1500U1640 1500A 1600A 4000A 纬轩机电130.00
GTP1600U1640 1600A 1600A 4000A 纬轩机电130.00
GTP1900U2050 1900A 2000A 5000A 纬轩机电130.00
GTP2000U2050 2000A 2000A 5000A 纬轩机电130.00
GTP2200U2550 2200A 2500A 5000A 纬轩机电130.00
GTP2400U2564 2400A 2500A 6400A6 纬轩机电130.00
GTP2500U2564 2500A 2500A 6400A6 纬轩机电130.00
GTP3000U3064 3000A 3000A 6400A6 纬轩机电130.00
GTP3200U3264 3200A 3200A 6400A6 纬轩机电130.00
GTP3600U4064 3600A 4000A 6400A6 纬轩机电130.00
GTP4000U4064 4000A 4000A 6400A6 纬轩机电130.00
GTP5000U5064 5000A 5000A 6400A6 纬轩机电130.00
GTP6000U6064 6000A 6000A 6400A6 纬轩机电130.00
2WavePro and AKR only. EntelliGuard? G min. trip plug is 150A.
3PowerBreak only. EntelliGuard? G min. trip plug is 150A.
4WavePro and AKR only. EntelliGuard? G min. sensor is 400A.
5PowerBreak only. EntelliGuard? G min. sensor is 400A.
6IEC only sensor, UL equivalents are 600A.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-17
to change without notice
Low Voltage Power and DC Circuit Breakers
EntelliGuard? TU Trip Unit
Conversion Kit Accessories and Hardware
Conversion Kit Accessories and Hardware
Description Product Number List Price GO Schedule
4 wire RELT & Ground Fault Alarm Harness kit. Used to add RELT or Ground Fault Alarm to an existing MVT
installation in combination with an EntelliGuard? TU. Harness comes with Breaker and Cubicle side, 8 feet
of wire, terminal block, and RELT Labels1 GTURHA 纬轩机电150.00 GO-104G
4 wire RELT & Ground Fault Alarm Harness kit. Used to add RELT or Ground Fault Alarm to an existing MVT
installation in combination with an EntelliGuard? TU. Harness comes with Breaker and Cubicle side, 8 feet of
wire, terminal block, and RELT Labels. Includes 9 Pin Harness for 24VDC, Communications, and Voltage Source. GTURHB 纬轩机电200.00 GO-104G
RELT Switch Kit: Includes the following: RELT Switch, Lockable cover, contacts, wire harness, warning labels GTURSK 纬轩机电485.00 GO-104G
Zone Selective Interlock Module TIM1 纬轩机电402.00 GO-245B
Power Leader Voltage Conditioners – Supplies isolated bus voltage signal to EntelliGuard? TU trip units PLVC1G01 纬轩机电200.00/set GO-104A
Power Leader Power Supply 1.5A power supply. Qty 15 trip units may be powered from a single power supply PLPS4G01 纬轩机电1250.00 GO-104A
GE Portable Test Kit – Used for testing phase currents, Ground Fault, disabling Ground fault, RELT, Trip Breaker GTUTK20 纬轩机电3000.00 GO-245B
Rating Plug Removal Tool TRTOOL 纬轩机电12.00 GO-135S
Set-up Software GTUSS 纬轩机电200.00 GO-329R
1RELT and Ground Fault Alarm require 24VDC. If 24VDC cable is required order GTURHB
EntelliGuard? TU Trip Units are compatible with MicroVersaTrip?, RMS9, EPIC RMS9, MicroVersaTrip? Plus and PM,
Enhanced MicroVersaTrip? Plus and PM Trip Units models.
Coming Soon:
Power Break? II in a Power Break? I (fixed and drawout)
EntelliGuard? G in AKD-5, AKD-6, AKD-8 switchgear line-ups
Contact factory for availability and options
Switchgear
2
2-18 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers Trip Unit
Accessories
Optional Remote Display—Features
—Provides safe, convenient closed-door access to breaker
metering, status and setup functions
—Available for use with either MicroVersaTrip? Plus or
MicroVersaTrip? PM trip units
—Rugged plastic NEMA Type 1 enclosure with LCD and keypad
—Mounts easily on outside of breaker compartment door
—Sealable, clear LEXAN protective cover over display and "Enter"
key prohibits unauthorized trip setting changes
—Connects to breaker trip unit via 20-pin plug-in cable for fast
installation
—Breaker trip unit operates independently if cable is disconnected
Optional Remote Display
Target Module
GE Trip Unit Portable Test Set
Optional Remote Display (for MicroVersaTrip?)
List Price
Accessory Type Product Number GO-104B
Remote Display w/ 6’ Cable REMDIS1 纬轩机电350.00
Replacement Cable REMDIS2 纬轩机电35.00
Target Module (for ProTrip?)
All ProTrip? conversion kits come with a target module.
Order another only for renewal purposes.
List Price
Product Number GO-104P
TARGET02P 纬轩机电285.00
GE Trip Unit Portable Test Set (for MicroVersaTrip? and ProTrip?)
Allows for self-tests and functioning trip/no trip tests. Operates on
batteries (not included) or 120 VAC source.
List Price
Product Number GO-245B
TVRMS2 纬轩机电3000.00
EntelliGuard? TU Test Set
Allows for self-tests and functioning trip/no trip tests. Operates on
batteries (not included) or 120 VAC source.
List Price
Product Number GO-245B
GTUTK20 纬轩机电3000.00
EntelliGuard? TU Test Set
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-19
to change without notice
Low Voltage Power and DC Circuit Breakers Trip Unit
Accessories
POWER LEADER? Power Supply
The POWER LEADER? power supply provides 24Vdc control power to MicroVersaTrip? PM trips units used on WavePro low voltage
power circuit breakers. The control power is required for the trip unit’s communication and protective relay functions.
List Price System Requirements
Description Product Number GO-104A (Not included with power supply)
1.5A power supply. PLPS4G01 纬轩机电1250.00 Input power, 100VA
Maximum wire length from power supply (85-265 Vac or 100-370 Vdc)
to trip device is 100 feet. A maximum of 45 trip
units may be powered from a single power supply.
POWER LEADER? Voltage Conditioner
Conditions and scales 120Vac to 1.76Vac for use by the trip unit for voltage sensing. Provides transient protection. Requires isolation
PTs with 120 volt secondary. Supports up to 15 trip units at a maximum distance of 20 feet. Required for PM trip units only.
List Price System Requirements
Description Product Number GO-104A (Not included with voltage conditioners)
Supplies isolated bus voltage signal PLVC1G01 纬轩机电200.00/set One set of 3 voltage conditioners required
to MicroVersaTrip? PM trip units. for each sensing location. PTs also required.
MicroVersaTrip? Portable Power Pack
The MicroVersaTrip? Portable Battery Pack is a maintenance power source used to power up trip units for setting or adjusting trip set
points or for reading trip targets when the trip unit is not otherwise energized. It is a redundant power source to the onboard battery
supplied with the Enhanced MicroVersaTrip? Plus and PM (5-button keypad) trip units. The portable battery pack connects to the trip
unit through the rating plug test jack. It requires three (3) standard 9Vdc alkaline batteries (not included).
List Price
Description Product Number GO-245A
MicroVersaTrip? Portable Power Pack TVPBP 纬轩机电75.00
MicroVersaTrip? and EntelliGuard? Rating Plug Removal Tool
List Price
Description Product Number GO-135S
MicroVersaTrip? and EntelliGuard? Rating Plug Removal Tool TRTOOL 纬轩机电12.00
Switchgear
2
2-20 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
Electrically Operated Racking Device
The electrically operated racking device allows maintenance
personnel the ability to be up to 30 feet away from a draw-out
breaker during the racking operation. This was typically only an
option with medium voltage switchgear. Now, GE offers this as an
option with low voltage switchgear.
The electric motor is operated using convenient 115V AC power
with a plug-in power cord. The gearbox is easily attached to the
front of the breaker with a sliding latch connection.
The low voltage racking devices can be used with any WavePro or
EntelliGuard? breaker. Large frame WavePro breakers (3200 Amp
and above)1 require an accessory kit and a retrofit door to
accommodate the device.
Allowing the user to be physically removed from the breaker
racking mechanics during operation provides a peace of mind
not usually available in a low voltage application.
1Manufactured before 9/1/05.
Easy and Safe Operation
PRESS!
A push of the button on a handheld
remote operator draws the breaker out
with a 115V AC motor in the gear box.
PRESS!
Another push of the button racks the
breaker back into place.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-21
to change without notice
Low Voltage Power and DC Circuit Breakers
Electrically Operated Racking Device
Technical Specifications
Remote operation through a cable-connected handheld control
—Permits control of gearbox and racking motor from remote
location, allowing the user to be remote from the breaker during
the racking procedure.
—Cable allows user to be up to 30 feet away from the breaker
and away from the arc flash center.
—Allows user to determine their location based on room layout.
—Simple start switch push button in handheld box.
Portable gearbox with full operator control
—Allows the user to easily move a draw-out circuit breaker
between CONNECT and DISCONNECT positions.
—Can be used with WavePro or EntelliGuard? breakers in
Entellisys?, AKD-10 or Power Break? switchboard line-ups (with
WavePro breakers).
—Motor directional switch for IN/OUT racking control.
—Circuit breaker reset toggle switch for control power.
Racking Device
—Electrically powered with 115V AC power (4 foot cord).
—Sliding latch allowing device to be easily attached to front of
breakers (WavePro or EntelliGuard?).
Retrofits (Product shipped before June 2005)
—Small Frame (800 - 2000 Amp) WavePro breakers accept the
Racking Device without modification.
—Existing Large Frame (3200 - 5000 Amp) WavePro breakers
compatible by simply replacing the cubicle door.
—All EntelliGuard? breakers accept the Racking Device without
modifications.
Racking Devices
Product Number Description
WPEGRRLV Remote Racking Device
WPEGRRMODL Large Frame Breaker
Modification Kit (3200-5000 Amp)
Retrofit Doors for Large Frame WavePro
Product Number Description
WPEGRRLFDR 3200/4000 Amp WavePro
WPEGRRLFDRDI 3200/4000 Amp WavePro
with defeatable interlock
WPEGRR50DR 5000 Amp WavePro
WPEGRR50DRDI 5000 Amp WavePro
with defeatable interlock
Breaker Cover
Latch Opening
AC Plug
Circuit Breaker - Reset Toggle Switch
IN/OUT Directional Toggle Switch
30 Foot Cable
Start Switch - Push Button
Handheld Control Box
Square Drive
- Coupling to Breaker
Sliding Latch
Gear Motor Housing
Switchgear
2
2-22 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
Reference Publications
General Installation and Maintenance
Publication Number Publication Name
DEH-136 WavePro Small Frame Maintenance Manual, WP-08-20
DEH-137 WavePro Large Frame Maintenance Manual, WP-32-50
DEH-178 User’s Guide - MicroVersaTrip? Plus/PM Trip Units
DEH-179 User’s Guide - Power+ Trip Unit
GEH-5945 Power Leader? Recommended Power Supplies
GEH-5946 Power Leader? Voltage Conditioner
DEJ-001 Portable Battery Power Pack
GEK-64467 Zone Selective Interlock Module
DEH-134 WavePro Small Frame User’s Manual, WP-08-20
DEH-135 WavePro Large Frame User’s Manual, WP-32-50
GEK-97367A User’s Guide TVRMS2 Programmer Portable Test Set
DEF-004 WavePro Small Frame (800-2000A) Renewal Parts Guide
DEF-005 WavePro Large Frame (3200-5000A) Renewal Parts Guide
DES-001 WavePro Time-Current Curves (LSI)
DES-002 WavePro Time-Current Curves (GF)
DES-026 WavePro Time-Current Curves (Special GF)
DET-167 WavePro Breaker Application Guide
DEP-080 WavePro Selection and Pricing Guide
DEE-194 WavePro User Publications Summary—WavePro
Breakers and AKD-10 Switchgear
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-23
to change without notice
Low Voltage Power and DC Circuit Breakers
Asbestos Free Arc Quencher Replacement Kits
GE’s Asbestos Free Arc Quencher Replacement Kits are designed
to replace asbestos plate style arc quenchers on AK and early
AKR power circuit breakers with reliable, proven steel plate style
arc quenchers used on modern AKR breakers. The kits have been
ANSI C37.59 tested for dielectric and short circuit ensuring breaker
performance to original specifications. On most AK series
breakers, no modifications are needed to install the arc quencher
replacement kit. Installation is typically done in less than one
hour (see Installation Instructions GEH-6464). Asbestos Free Arc
Quencher replacement kits are shipped complete with detailed
installation instructions and everything you need for fast and
easy arc quencher replacement:
—Asbestos free metal plate or ceramic arc quenchers
—Contact guides and arc runners (when required)
—Asbestos free replacement barriers (when required)
—All required mounting hardware
Product Number Selection
Reference Publications
Asbestos Free Arc Quencher Replacement Kits DET-096
Installation Instructions GEH-6464
Arc Quenchers Replacement Kit
AKO25 G1 AQR1
Breaker
AK-15
AK-25
AKU-25
AKR-30S
AKR-30
AKRU-30
AKR-30H
AKRU-30H
AK-50
AKT-50
AKU-50
AKJ-50
AKJT-50
AKJU-50
AKR-50
AKRT-50
AKRU-50
AKJ-50H
AKJT-50H
AKJU-50H
AKR-50H
AKRT-50H
AKRU-50H
AKJ-50
AKJT-50
AKJU-50
AKJ-50H
AKJT-50H
AKJU-50H
AK-75
AKR-75
AK-100
AKR-100
Model Application
For Asbestos Removal G1
Renewal Kit for G2
Ceramic Arc Quenchers
AKO25 1,2,3
AKR3S 1,2
AKR30
AKR3H
AKR50
AKO50 2,3
AKR5H
AKD50 4
AKD5H 4
AKR10 2
AKO75 2,3
AKR75 2
AKO10 2,3
AQR1 Arc Quencher Replacement Kit
Generation 1
1Kits contain replacement barriers only, arc quenchers do not contain asbestos.
2G2 kits are not available for these breakers, please contact the factory for individual replacement arc quenchers.
3Does not apply to AK-1 series breakers.
4These kits are for use on breakers used in AKD and AKD-5 switchgear and substructures.
Price Selection
Select the desired product number from the above chart. Match
the product prefix with the product number in the first column of
the pricing table. Select the application column that matches the
product suffix chosen. The price is found in the intersecting box.
G1 G2
AKO25AQR1 纬轩机电800.00 —
AKR3SAQR1 纬轩机电800.00 —
AKR30AQR1 纬轩机电2000.00 纬轩机电2000.00
AKR3HAQR1 纬轩机电2300.00 纬轩机电2300.00
AKO50AQR1 纬轩机电2350.00 —
AKR50AQR1 纬轩机电2000.00 纬轩机电2000.00
AKR5HAQR1 纬轩机电2300.00 纬轩机电2300.00
AKD50AQR1 纬轩机电2000.00 纬轩机电2000.00
AKD5HAQR1 纬轩机电2300.00 纬轩机电2300.00
AKO75AQR1 纬轩机电2900.00 —
AKR75AQR1 纬轩机电2700.00 —
AKO10AQR1 纬轩机电3600.00 —
AKR10AQR1 纬轩机电3250.00 —
Product Number
List Price, GO-104B
Switchgear
2
2-24 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Notes
Section 3: Motor Control Centers
Table of Contents
Motor Control Centers
3
Prices and data subject Aftermarket Catalog www.geelectrical.com 3-1
to change without notice
History/Timeline ...........................................................................3-2
Motor Control Centers - Low Voltage
Introduction..................................................................................................3-3
EVOLUTION SERIES E9000?, Key Benefits ......................................3-4
Short/Mid Cycle Program ......................................................................3-5
Renewal Parts
EVOLUTION SERIES E9000? ..............................................................3-6
GE Fastrac Program MCC Units Quick Selection Guide
CR8000, Spectra?..................................................................................3-7
Renewal Parts
7700-Line, 8000-Line & Spectra? Series .................................3-12
Motor Control Centers - Medium Voltage
Limitamp
2400-7200 volts..................................................................................3-15
Main Contactor Replacements
and Conversions ...........................................................................3-18
Renewal Parts - CR194 and CR7160 ........................................3-19
GE CR 7069 Synchronous Motor Control
Field Panels ............................................................................3-21
E9000
EVOLUTION SERIES E9000?/Spectra?/8000 Low Voltage Motor
Control Centers
Product References:
Engineered Products Catalog Section 10
Application and Selection Guide E9000 DET291A
Application and Selection Guide Spectra/8000 GET6729
Motor Control Center Units (Starters and Feeders)
GE Fastrac Program: 1 week
Product References:
Engineered Products Catalog Section 10
DE-415 Quick Selection Software (3 1/2" diskette)
Fastrac items are listed in red type.
This catalog contains replacement parts, retrofits, accessories,
and older generation products. For current generation products,
please see the GE BuyLog? or Control Catalog.
Motor Control Centers
3-2 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Limitamp
Medium Voltage History/Timeline
1949 1st oil-immersed contactor & fuse starter, 54”W x 60”D
1955 1st front-connected, roll-out Air Break starter
1960 1st fully drawout medium voltage starter
1966 Swing-open contactor, 3-high construction introduced
1972 700 Amp contactor, 2-high contactor design, SPM
1980 Hybrid 400 Amp vacuum contactor introduced
1985 Vacuum Limitamp, uSPM for synchronous motors
1994 CR194 2-high stationary introduction
1995 CR194 2-high drawout introduction
2000 400A Soft Starter
2002 800A Soft Starter
2003 3000A Bus
2007 CR194 1-high UL drawout introduction
Motor Control Centers
History/Timeline
The Evolution to E9000
Low Voltage Transformers History/Timeline
1948 CR7097 Schenectady NY
1952 IC7092 Salem VA
DA7093 & 7098 Seattle, WA./San Leandro, CA.
DA7092 North Hollywood
DA7093 Norwood, OH.
1960 7700 Line
1975 2700 Line
1980 8000 Line
1996 SPECTRA
2003 Evolution Series E9000
3
This catalog contains replacement parts, retrofits, accessories,
and older generation products. For current generation products,
please see the GE BuyLog? or Control Catalog.
Motor Control Centers
3
Prices and data subject Aftermarket Catalog www.geelectrical.com 3-3
to change without notice
Motor Control Centers—Low Voltage
GE Motor Control Centers
Introduction
GE motor control centers offer an ideal means of quickly providing
centralized motor control and other related control equipment.
A pre-engineered version of the GE motor control center is available
at short-cycle and mid-cycle shipment. The product scope
available is more limited than with normal cycle shipments, and
includes certain combination starter units, feeder units, distribution
transformers, lighting panels, relaying panels, programmable
controllers and other miscellaneous devices to be installed in a
single, floor-mounted enclosure and fed from a common
enclosed horizontal and vertical bus system.
Each GE motor control center vertical section is constructed of
0.090-inch (13-gauge) steel which is subjected to a special corrosion-resistant
zinc-phosphate treatment followed by a powder
paint process using ANSI-61 light gray alkyd-enamel paint. Each
section houses the horizontal and vertical bus, horizontal and
vertical wireways and the compartmentalized individual control
units. Standard unit construction is Class I Type B wiring1. Factory
assembled, wired and tested units are mounted in each vertical
section, and sections are easily bolted together to form a motor
control center line-up. The entire line-up is then powered by a
single incoming-line connection.
Standard UL labeled NEMA 1 enclosure contains 600-ampere,
three-phase, copper tin-plated horizontal main bus, 300-ampere,
three-phase, copper tin-plated vertical bus and is braced to
withstand a fault current of 65,000 rms symmetrical. Each vertical
section must be priced to include 72 inches of vertical space
units consisting of starters, feeders, transformers, panels, incoming
terminal boards and/or enclosure spaces for future units.
1Typical diagrams can be found in the Application and Selection Guide for DET291
Section “L”.
Motor Control Centers
3
3-4 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Motor Control Centers—Low Voltage
GE Motor Control Centers
EVOLUTION SERIES E9000? Key Benefits
Safety:
—No Hot bus rework up to 600A
—Hi-Visible Trip Indication
—Door and unit interlocks
—UBC Seismic Zone 4 Standard
—Six Sigma Designed
Size:
—6" reduction—Sz 3, 5
—6" to 36" reduction VFD’s
—6" Size 1 FVNR
—6" 150A Feeder
—12" 250A Feeder
—36" Size 5 Plug-In, two in a section
—300VA CPT—No additional Space
—Plug In Buckets to Size 5
—Plug In Feeders to 600A
Simplicity:
—Easy Unit Insertion/Removal
—Snap-In Shelves
—Easily Quoted… Fastrac MCCs
—Manufacturing Flexibility
Scope:
—450 Hp VFD’s
—500 Hp SSS
—250A and 600A Stabs
—TVSS 65-200K Surge Current
—Automatic Transfer Switches to 1200A
Motor Control Centers
3
Prices and data subject Aftermarket Catalog www.geelectrical.com 3-5
to change without notice
Motor Control Centers—Low Voltage
GE Motor Control Centers
Short/Mid Cycle Program
Features
The Evolution SC/MC is a pre-engineered, factory assembled, fully
tested motor control center that contains all the standard features
of the Evolution motor control center, including some
options.
All sections and units will be UL labeled where possible. Refer to
Company if labeling is critical.
Please contact your distributor or GE for scope, pricing, and
ordering.
No changes are allowed to Evolution SC/MC bill-ofmaterial
after order entry.
Highlights of the Evolution SC/MC Program:
I Structure (20-inch wide is standard)
—13- or 20-inch deep
—Back-to-back mounting (20-inch deep only)
—NEMA 1 gasket, 2, 12, 3R non-walk-in
—24-inch wide enclosures
—Corner section enclosures
—Special enclosures
—Engraved nameplates (optional)
—Addition of “Field Installed Kits”
II Bus Systems
—Voltage: 208, 240, 480, 575 volts
—3-phase, 3-wire, or 3-phase, 4-wire
—Main bus: 600, 800, 1000, 1200 ampere
—Vertical bus: 300, 450, 600 ampere, section-by-section
—Optional ground bus: 300, 375, 600 ampere
—Neutral bus: 300, 400, 600, 800, 1000 ampere
—Optional silver plating
—Back-to-back construction (rear vertical bus)
—“Vertical Bus Plugs” installed in unused stab openings
III Incoming Line
—600 amperes with 18 inches of pull space
—Circuit breakers thru 1200 amperes
—Fusible switches thru 600 amperes
IV Feeders and Mains
—Feeders—800-ampere Spectra
—Feeders—600-ampere fused switch
—Main—1200-ampere Spectra
—Shunt trip and UV release
V Combination Starter Units
—Control Power Transformer (CPT) (optional)
—“Extra” auxiliary interlocks (optional)
—Line-to-line control
—Line-to-neutral control
—Separate control power or common CPT
—FVNR—Size 1 thru 6
—FVR—Size 1 thru 4
—RVNR—Size 2 thru 5
—2S2W—Size 1 thru 4
—2S1W—Size 1 thru 4
—NEMA Type 1B wiring
—Interlocks mounted on circuit breaker and
fusible switch (optional)
Motor Control Centers
3
3-6 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Motor Control Centers—Low Voltage
Frequently Requested Motor Control Center Renewal Parts
EVOLUTION SERIES E9000?