今日最新资讯
热门资讯
国内新闻
    ABB sdcs-IOB-21
    发布者:weixuan006  发布时间:2024-05-07 10:30:29  访问次数:


    BCU Burner control unit
    370 Series 370
    Q Mains voltage 120 V AC, 50/60 Hz
    W Mains voltage 230 V AC, 50/60 Hz
    — Without ignition
    I1 Electronic ignition, single-pole
    I2 Electronic ignition, double-pole
    I3 Electronic ignition, double-pole with neutral conductor
    F Fan control
    E Valve control
    U0 Ionization control (continuous op.) or UV control (intermittent op. with UVS)
    U1 UV control (continuous operation with UVD 1)
    D1 DGmax. monitoring
    D3 Integrated tightness control
    B1 PROFIBUS DP interface
    -3 Three-point step control via PROFIBUS DP
    For controlling, igniting and monitoring industrial forced draught burners of unlimited
    capacity in intermittent or continuous operation (in conjunction with UV sensor UVS, only
    intermittent operation available) for applications pursuant to EN 676.
    It can be used for directly ignited forced draught burners or forced draught burners
    ignited with a gas pilot. Programmable via an optical interface and the PC software
    BCSoft, with optional quick start without pre-purge, display of the program status, unit
    parameters and flame signal, integrated Manual mode for manual burner start, BCU
    370..D3 with tightness control function, BCU 370..B1 with PROFIBUS DP interface,
    can be programmed according to customer requirements, EU certified, AGA, FM, CSA
    (USA, Canada) and EAC approved, UL listed.
    Designation Order no.
    Without ignition; DGmax. monitoring
    BCU 370WFEU0D1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88600015
    Without ignition; integrated tightness control
    BCU 370WFEU0D3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88600023
    Electronic ignition, single-pole*; DGmax. monitoring
    BCU 370WI1FEU0D1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88600001
    Electronic ignition, single-pole*; integrated tightness
    control
    BCU 370WI1FEU0D3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88600206
    Versions
    BCU 370..B1 with PROFIBUS DP interface,
    connection in the lower section of the housing . . . . . . . . . . . . . . . . surcharge
    BCU 370..B1-3 with three-point step control
    via PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . surcharge
    * Note the cable length and ignition energy (cf. Technical Information)
    BCU 370 Technical
    Information
    BCU 370
    6 Electric flame monitoring and control units
    2-90
     
    Burner control units BCU 570
    Type code
    BCU Burner control unit
    570 Series 570
    Q Mains voltage 120 V AC, 50/60 Hz
    W Mains voltage 230 V AC, 50/60 Hz
    C0 No valve proving system
    C1 Valve proving system
    F1 Modulating with IC interface
    F2 Modulating with RBW interface

免责声明:焊材网转载作品均注明出处,本网未注明出处和转载的,是出于传递更多信息之目的,并不意味 着赞同其观点或证实其内容的真实性。如转载作品侵犯作者署名权,或有其他诸如版权、肖像权、知识产权等方面的伤害,并非本网故意为之,在接到相关权利人通知后将立即加以更正。联系电话:0571-87774297。