商铺名称:上海斌勤电气技术有限公司
联系人:康奎(先生)
联系手机:
固定电话:
企业邮箱:192061030@qq.com
联系地址:上海市松江区三新北路1800弄(松江电子商务园区)
邮编:201501
联系我时,请说是在焊材网上看到的,谢谢!
西门子电源模块6SL3130-7TE28-0AA3
6SL3130-7TE28-0AA3
公司代理西门子全系列产品为西门子中国总代理西门子工业自动化与驱动技术全系列产品全国一级西门子PLC/触摸屏/变频器/数控/伺服/电源/模块/CP5611网卡/电缆/电池/接头/连接器等自动化与驱动技术
各位顾客,本公司所经营产品均为西门子正品原装货,质量保证,请您放心。需要价格及规格型号技术参数 请大家提前联系电话咨询(微信)18621061383,QQ:192061030以便确定货期和价格。
In conjunction with Active Interface Modules and a logically consistent configuration of the plant or system, line filters limit the interference conducted by the power modules to the limit values of Category C2 acc. to EN 61800‑3. Line filters are only suitable for direct connection to TN line systems.
Note:
According to product standard EN 61800‑3, RFI suppression commensurate with the relevant rated conditions must be provided and is a legal requirement in the EU (EMC Directive). Line filters and line reactors are required for this purpose. The use of line filters of other makes can lead to limit value violations, resonance, overvoltages and irreparable damage to motors or other equipment. The machine manufacturer must provide verification that the machinery to be operated with the drive products and the installed suppression elements, e.g. line filters, are CE-EMC-compliant.
Optional Basic Line Filters that are coordinated with the power ranges in booksize format are available for the SINAMICS S120 drive system.
Basic Line Filter
With the Basic Line Filters in combination with the Active Interface Modules, the limits for the interference voltages can be extended to Category C2 (EN 61800-3) or, retaining Category C3, longer total cable lengths are possible for the configuration.
Basic Line Filters are used on machines on which conducted interference emissions in the frequency range between 150 kHz and 30 MHz need to be damped in accordance with the requirements of CE-EMC legislation.